Sign in
Refrigeration and Air Conditioning Mechanic Math
Online Red Seal Exam Preparation, built on official standardsMathQuestion 4 of 1070% to goContinue at question 4
10 questions
2 right · 1 wrong · 7 to do- 1Superheat at the evaporator outlet
- 2Sensible capacity of a cooling coil
- 3Chiller capacity from a metric flow
- 4Gauge pressure to absolute pressure
- 5Air flow in a rectangular duct
- 6Blower speed from the pulley sizes
- 7Heat gain through a cooler wall
- 8Refrigerant charge in pounds
- 9Duct velocity from a pitot tube reading
- 10COP of a heat pump in heating
Part 1
2 right · 1 wrong · 7 to do- 1Superheat at the evaporator outletSuperheat = line temperature − saturation temperature · Procedural and application
- 2Sensible capacity of a cooling coilQ = CFM × 1.08 × ΔT · Procedural and application
- 3Chiller capacity from a metric flowBtuh = 500 × USGPM × Δ°F · Critical thinking
- 4Gauge pressure to absolute pressurepsia = psig + 14.7 · Knowledge and recall
- 5Air flow in a rectangular ductCFM = velocity × area · Procedural and application
- 6Blower speed from the pulley sizesd₁ × rpm₁ = d₂ × rpm₂ · Procedural and application
- 7Heat gain through a cooler wallBtuh = U × A × ΔT, with U = 1 ÷ R · Procedural and application
- 8Refrigerant charge in poundsConversion · Procedural and application
- 9Duct velocity from a pitot tube readingVelocity = 4 005 × √q · Procedural and application
- 10COP of a heat pump in heatingCOP = heat delivered ÷ heat equivalent of the power input · Critical thinking
By question type
- Procedural and application2 of 7 done
- Critical thinking1 of 2 done
- Knowledge and recall0 of 1 done