AC power, power factor and three-phase loads
S: apparent power in VA · P: real power in W · PF: decimal power factor. Three-phase formulas assume a balanced load; use RMS voltage/current.
- S₁φ = VI
- P₁φ = VI × PF
- S₃φ = √3 × Vline × Iline
- P₃φ = √3 × Vline × Iline × PF = 3 × Vphase × Iphase × PF
- PF = P/S = cos φ (sinusoidal voltage and current)
- 1Identify single-phase or balanced three-phase and line versus phase quantities.
- 2Calculate VA first, then multiply by PF for watts. Divide by 1000 for kVA or kW.
A balanced 400 V, 10 A load at PF = 0.80 uses P = √3 × 400 × 10 × 0.80 ≈ 5.54 kW.
- √3 × volts × amperes produces VA, not kVA.
- PF = cos(φ), not cos multiplied by an angle.
Pass Your Red Seal’s lessons and practice are independent study material. Source: OpenStax: power in an AC circuit
Try one
A single-phase load uses 2400 W and 3000 VA. What is its power factor?