Pass Your Red Seal
MathOnline Red Seal Exam Preparation, built on official standards

Refrigeration and Air Conditioning Mechanic formula sheet

MathReference123 formulas · 86 conversions · 109 acronyms
All math

On the exam

Official formula sheet
Given at the exam
Conversions
Partly given
Acronyms
You get the list
Calculator
The same calculator as here

On the exam

Formula sheetGiven at the exam
CalculatorThe same as here

Formulas

123 formulas

From the official Refrigeration and Air Conditioning Mechanic formula sheet. The same sheet is printed for you at the exam.

Btuh4.5 × CFM × ∆ H
Btuh500 × USGPM × ∆ ˚ F
BtuhU × a in ft2 × ∆ ˚ F
CFMv in fpm × a in ft2
Cooling coefficient of performance (COP)COP = NRE / (THR − NRE)
Diameterd1 × rpm1 = d2 × rpm2
Enthalpy change∆ U + ( P ∆ V )
Expansionl × ∆ T × α
ForceP × a
Water flow (US gpm)US gpm ≈ Q / (500 × ΔT)
Liquid flow (US gpm)US gpm = Q / (60 × ρ × c × ΔT)
Grade(drop or rise) / (run)
Outdoor supply air volume (%)(OA %) / (100)
Hydrostatic pressure rise (Pa)ΔP = ρ × g × h
psiapsig + 14.7
psigpsia − 14.7
Sensible air heat rate (Btu/h)Q ≈ 1.08 × CFM × ΔT
Q (Btuh)USGPM × 500 × ∆ ° F
Airflow (CFM)CFM ≈ (P × 3.412) / (1.08 × ΔT)
R- value1 / U
Temperature difference(Btuh) / (500 × gpm)
Total supply airOA % + RA % = SA
U-factor1 / R
U-factor (SI unit)W / (m2 × K)
Velocity4 005 × √(q)
Water heat rate (Btu/h)Q ≈ 500 × US gpm × ΔT
Air heat rate (Btu/h)Q ≈ 4.5 × CFM × Δh
Btuh4.5 × CFM × ∆ H
gpm(Btuh) / (500 × ∆ T of water)
Circleπ ⁢ r2
Cylinder (open top)π ⁢ r2 + π ⁢ d ⁢ h
Cylinder (totally enclosed)2 ⁢ π r2 + π ⁢ d ⁢ h
Rectanglel × w
Rectangle box (open top)( l × w ) + 2 ( w × h ) + 2 ( l × h )
Rectangle box (totally enclosed)2 ( L × w ) + 2 ( w × h ) + 2 ( L × h )
Sphere4 π ⁢ r2
Triangle(B × h) / (2)
Cylinderπ ⁢ r2 ⁢ h
Cuboidl × w × h
Sphere(4 ⁢ π ⁢ r3) / (3)
Aampere
BTUBritish thermal unit
BtuhBritish thermal units per hour
BTU/lbBritish thermal units per pound
CFMcubic feet per minute
dBAA-weighted decibel
°Cdegree Celsius
°Fdegree Fahrenheit
ft.foot
ft²square foot
ft³cubic foot
fpmfeet per minute
gal.imperial gallon
hheight
hphorsepower
hrhour
Hzhertz
in.inch
in²square inch
Kkelvin
kgkilogram
kPakilopascal
kPaGkilopascal gauge
llength
Llitre
lb.pound
mmetre
m²square metre
m³cubic metre
mAmilliampere
mmmillimetre
mVmillivolt
oz.ounce
psipounds per square inch
psiapounds per square inch absolute
psigpounds per square inch gauge
rpmrevolutions per minute
ssecond
timperial ton
USGUnited States gallon
USGPMUnited States gallons per minute
Vvolt
VAvolt-ampere
VACvolts alternating current
VDCvolts direct current
wwidth
Wwatt
w.c.water column
π3.1416
1 US gal of waterapproximately 8.33 lb mass
12,000 Btu/h1 refrigeration ton
1,000 W of real powerapproximately 3,412 Btu/h
Balanced three-phase real powerP = √3 × line voltage × line current × power factor
Pressure head conversion unit0.433 psi/ft.
Standard-air sensible heat-rate factor1.08 Btu/(h·CFM·°F)
Standard-air mass-flow factor4.5 lb/(h·CFM)
αcoefficient of expansion
Area (a)space occupied by a 2 - dimensional figure
Bbase
cspecific heat capacity
ddiameter
∆Eenergy change — i.e. change in energy of a system at constant volume
∆Henthalpy change — i.e. change in energy of a system at constant pressure (BTU/lb).
∆Pdifference in pressure
∆psigdifference in pounds per square inch gauge
∆Tdifference in temperature
∆Uinternal energy change
dens.density
Mmass
NREnet refrigeration effect
OAoutdoor air
Ppressure
qvelocity pressure (dynamic pressure)
Qquantity of heat
rradius
Rthermal resistance
RAreturn air
R-valueresistance to conductive flow of heat
SAtotal supply air
THRtotal heat of rejection
Uthermal transmittance
U-factoroverall heat transfer coefficient
Velocity (v)speed of motion in a given direction
General formulas
Btuh4.5 × CFM × ∆ H
Btuh500 × USGPM × ∆ ˚ F
BtuhU × a in ft2 × ∆ ˚ F
CFMv in fpm × a in ft2
Cooling coefficient of performance (COP)COP = NRE / (THR − NRE)
Diameterd1 × rpm1 = d2 × rpm2
Enthalpy change∆ U + ( P ∆ V )
Expansionl × ∆ T × α
ForceP × a
Water flow (US gpm)US gpm ≈ Q / (500 × ΔT)
Liquid flow (US gpm)US gpm = Q / (60 × ρ × c × ΔT)
Grade(drop or rise) / (run)
Outdoor supply air volume (%)(OA %) / (100)
Hydrostatic pressure rise (Pa)ΔP = ρ × g × h
psiapsig + 14.7
psigpsia − 14.7
Sensible air heat rate (Btu/h)Q ≈ 1.08 × CFM × ΔT
Q (Btuh)USGPM × 500 × ∆ ° F
Airflow (CFM)CFM ≈ (P × 3.412) / (1.08 × ΔT)
R- value1 / U
Temperature difference(Btuh) / (500 × gpm)
Total supply airOA % + RA % = SA
U-factor1 / R
U-factor (SI unit)W / (m2 × K)
Velocity4 005 × √(q)
Total thermal formulas
Water heat rate (Btu/h)Q ≈ 500 × US gpm × ΔT
Air heat rate (Btu/h)Q ≈ 4.5 × CFM × Δh
Btuh4.5 × CFM × ∆ H
gpm(Btuh) / (500 × ∆ T of water)
Area formulas
Circleπ ⁢ r2
Cylinder (open top)π ⁢ r2 + π ⁢ d ⁢ h
Cylinder (totally enclosed)2 ⁢ π r2 + π ⁢ d ⁢ h
Rectanglel × w
Rectangle box (open top)( l × w ) + 2 ( w × h ) + 2 ( l × h )
Rectangle box (totally enclosed)2 ( L × w ) + 2 ( w × h ) + 2 ( L × h )
Sphere4 π ⁢ r2
Triangle(B × h) / (2)
Volume formulas
Cylinderπ ⁢ r2 ⁢ h
Cuboidl × w × h
Sphere(4 ⁢ π ⁢ r3) / (3)
Measurement unit abbreviations
Aampere
BTUBritish thermal unit
BtuhBritish thermal units per hour
BTU/lbBritish thermal units per pound
CFMcubic feet per minute
dBAA-weighted decibel
°Cdegree Celsius
°Fdegree Fahrenheit
ft.foot
ft²square foot
ft³cubic foot
fpmfeet per minute
gal.imperial gallon
hheight
hphorsepower
hrhour
Hzhertz
in.inch
in²square inch
Kkelvin
kgkilogram
kPakilopascal
kPaGkilopascal gauge
llength
Llitre
lb.pound
mmetre
m²square metre
m³cubic metre
mAmilliampere
mmmillimetre
mVmillivolt
oz.ounce
psipounds per square inch
psiapounds per square inch absolute
psigpounds per square inch gauge
rpmrevolutions per minute
ssecond
timperial ton
USGUnited States gallon
USGPMUnited States gallons per minute
Vvolt
VAvolt-ampere
VACvolts alternating current
VDCvolts direct current
wwidth
Wwatt
w.c.water column
Constants
π3.1416
1 US gal of waterapproximately 8.33 lb mass
12,000 Btu/h1 refrigeration ton
1,000 W of real powerapproximately 3,412 Btu/h
Balanced three-phase real powerP = √3 × line voltage × line current × power factor
Pressure head conversion unit0.433 psi/ft.
Standard-air sensible heat-rate factor1.08 Btu/(h·CFM·°F)
Standard-air mass-flow factor4.5 lb/(h·CFM)
Values
αcoefficient of expansion
Area (a)space occupied by a 2 - dimensional figure
Bbase
cspecific heat capacity
ddiameter
∆Eenergy change — i.e. change in energy of a system at constant volume
∆Henthalpy change — i.e. change in energy of a system at constant pressure (BTU/lb).
∆Pdifference in pressure
∆psigdifference in pounds per square inch gauge
∆Tdifference in temperature
∆Uinternal energy change
dens.density
Mmass
NREnet refrigeration effect
OAoutdoor air
Ppressure
qvelocity pressure (dynamic pressure)
Qquantity of heat
rradius
Rthermal resistance
RAreturn air
R-valueresistance to conductive flow of heat
SAtotal supply air
THRtotal heat of rejection
Uthermal transmittance
U-factoroverall heat transfer coefficient
Velocity (v)speed of motion in a given direction

On the exam

ConversionsPartly given

Conversions

86 conversions
°C → °F× 1.8 and add 32
ft² → in²× 144
ft³ → USG× 7.48
kg → lb.× 2.205
kPa → lbf/ft²× 20.88
kPa → lbf/in² (psi)× 0.1450
L → US gal× 0.26417
L/min → USGPM× 0.2641
L/s → Imperial gpm× 13.20
m → ft.× 3.281
m² → ft²× 10.76
m³ → ft³× 35.31
mm → in.× 0.03937
1 psi6.895 kPa
1 kPa0.1450 psi
1 bar100 kPa
1 bar14.50 psi
1 atm101.3 kPa
1 atm14.70 psi
1 in w.c.249.1 Pa
1 ft of water0.4335 psi
1 in Hg3.386 kPa
1 lbf4.448 N
1 kN224.8 lbf
°C to °F× 1.8, then + 32
°F to °C− 32, then ÷ 1.8
°C to K+ 273.15
A difference of 1 °C1.8 °F
Water freezes0 °C = 32 °F
Water boils (sea level)100 °C = 212 °F
1 hp746 W
1 kW1.341 hp
1 kW3 412 Btu/h
1 Btu/h0.2931 W
1 Btu1.055 kJ
1 ton of refrigeration12 000 Btu/h
1 ton of refrigeration3.517 kW
1 kWh3.6 MJ
1 therm100 000 Btu
1 boiler hp33 475 Btu/h
1 L/s60 L/min
1 L/s3.6 m³/h
1 L/s15.85 US gpm
1 L/s13.20 imp gpm
1 US gpm3.785 L/min
1 imp gpm4.546 L/min
1 cfm0.4719 L/s
1 cfm1.699 m³/h
1 m³/h0.5886 cfm
1 m³1 000 L
1 m³35.31 ft³
1 m³1.308 yd³
1 yd³27 ft³
1 ft³28.32 L
1 ft³7.481 US gal
1 ft³6.229 imp gal
1 L0.2642 US gal
1 L0.2200 imp gal
1 US gal3.785 L
1 imp gal4.546 L
1 in³16.39 mL
1 ft²144 in²
1 ft²0.0929 m²
1 m²10.76 ft²
1 yd²9 ft²
1 yd²0.8361 m²
1 ha10 000 m²
1 ha2.471 acres
1 acre4 047 m²
1 in25.4 mm
1 ft304.8 mm
1 ft0.3048 m
1 yd0.9144 m
1 m3.281 ft
1 m39.37 in
1 km0.6214 mi
1 mi1.609 km
Water1 000 kg/m³ = 1 kg/L
Water62.4 lb/ft³
Water8.34 lb per US gal
Water10.0 lb per imp gal
Steel7 850 kg/m³ = 490 lb/ft³
Steel plate7.85 kg per m² per mm
Concrete2 400 kg/m³ = 150 lb/ft³
1 kg/m³0.06243 lb/ft³
1 lb/ft³16.02 kg/m³
On your sheet
°C → °F× 1.8 and add 32
ft² → in²× 144
ft³ → USG× 7.48
kg → lb.× 2.205
kPa → lbf/ft²× 20.88
kPa → lbf/in² (psi)× 0.1450
L → US gal× 0.26417
L/min → USGPM× 0.2641
L/s → Imperial gpm× 13.20
m → ft.× 3.281
m² → ft²× 10.76
m³ → ft³× 35.31
mm → in.× 0.03937
Pressure and force
1 psi6.895 kPa
1 kPa0.1450 psi
1 bar100 kPa
1 bar14.50 psi
1 atm101.3 kPa
1 atm14.70 psi
1 in w.c.249.1 Pa
1 ft of water0.4335 psi
1 in Hg3.386 kPa
1 lbf4.448 N
1 kN224.8 lbf
Temperature
°C to °F× 1.8, then + 32
°F to °C− 32, then ÷ 1.8
°C to K+ 273.15
A difference of 1 °C1.8 °F
Water freezes0 °C = 32 °F
Water boils (sea level)100 °C = 212 °F
Power and energy
1 hp746 W
1 kW1.341 hp
1 kW3 412 Btu/h
1 Btu/h0.2931 W
1 Btu1.055 kJ
1 ton of refrigeration12 000 Btu/h
1 ton of refrigeration3.517 kW
1 kWh3.6 MJ
1 therm100 000 Btu
1 boiler hp33 475 Btu/h
Flow
1 L/s60 L/min
1 L/s3.6 m³/h
1 L/s15.85 US gpm
1 L/s13.20 imp gpm
1 US gpm3.785 L/min
1 imp gpm4.546 L/min
1 cfm0.4719 L/s
1 cfm1.699 m³/h
1 m³/h0.5886 cfm
Volume
1 m³1 000 L
1 m³35.31 ft³
1 m³1.308 yd³
1 yd³27 ft³
1 ft³28.32 L
1 ft³7.481 US gal
1 ft³6.229 imp gal
1 L0.2642 US gal
1 L0.2200 imp gal
1 US gal3.785 L
1 imp gal4.546 L
1 in³16.39 mL
Area
1 ft²144 in²
1 ft²0.0929 m²
1 m²10.76 ft²
1 yd²9 ft²
1 yd²0.8361 m²
1 ha10 000 m²
1 ha2.471 acres
1 acre4 047 m²
Length
1 in25.4 mm
1 ft304.8 mm
1 ft0.3048 m
1 yd0.9144 m
1 m3.281 ft
1 m39.37 in
1 km0.6214 mi
1 mi1.609 km
Density and unit mass
Water1 000 kg/m³ = 1 kg/L
Water62.4 lb/ft³
Water8.34 lb per US gal
Water10.0 lb per imp gal
Steel7 850 kg/m³ = 490 lb/ft³
Steel plate7.85 kg per m² per mm
Concrete2 400 kg/m³ = 150 lb/ft³
1 kg/m³0.06243 lb/ft³
1 lb/ft³16.02 kg/m³

On the exam

AcronymsYou get the list

Acronyms

109 acronyms

The following acronyms used in this trade may be on its Red Seal exam. They will also be provided with the exam sitting. The official list (PDF)

Aampere
A/Cair conditioning / air conditioner
ABalkylbenzene
ACalternating current
AHJauthority having jurisdiction
ANT.anticipator
ASHRAEAmerican Society of Heating, Refrigerating and Air-Conditioning Engineers
BTUBritish thermal unit
BTU/lbBritish thermal units per pound
BtuhBritish thermal units per hour
C.E.C.Canadian Electrical Code
CFHcubic feet per hour
CFMcubic feet per minute
cmcentimetre
COPcoefficient of performance
CPRcrankcase pressure regulator
CRACcomputer room air conditioning
CSACanadian Standards Association
CSIRcapacitor start / induction run rotor
dBAA-weighted decibel
DHUMdehumidifier
DIPdual in-line package
DPDTdouble-pole, double-throw
DTFDdefrost terminate fan delay
DXdirect expansion
ECMelectronic control module
EEVelectronic expansion valve
EPRevaporator pressure regulator
ERVenergy recovery ventilation
EXVelectric expansion valve
FLAfull load amperage
fpmfeet per minute
ft.foot
GFCIground fault circuit interrupter
GNDground
Hgmercury
hphorsepower
HRVheat recovery ventilator
HVACheating, ventilation and air conditioning
HVAC/Rheating, ventilation, air conditioning and refrigeration
Hzhertz
IDinside diameter
IMDGInternational Maritime Dangerous Goods
in²square inch
inHginches of mercury
inHg vacinches of mercury vacuum
IRinfrared
ISOInternational Organization for Standardization
JOHSCJoint Occupational Health and Safety Committee
kPaGkilopascal gauge
lb.pound
LEDlight-emitting diode
LLSVliquid line solenoid valve
LOTOlock-out and tag-out
LPSlow pressure switch
LRlong radius
mmmillimetre
MOmineral oil
NCnormally closed
NOnormally open
NTCnegative temperature coefficient
OAToutside air temperature
ODoutside diameter
OFCoil failure control
OFMoutdoor fan motor
OHSOccupational Health and Safety
ORDopen on rise of differential
ORIopen on rise of inlet
OROopen on rise of outlet
P/Epressure enthalpy
P/Tpressure temperature
POEpolyolester
PPEpersonal protective equipment
PSCpermanent split capacitor
psipounds per square inch
psiapounds per square inch absolute
psigpounds per square inch gauge
PTACpackaged terminal air conditioner
PTCpositive temperature coefficient
°Cdegree Celsius
°Fdegree Fahrenheit
R / °RRankin scale
R.H.relative humidity
rpmrevolutions per minute
RTUrooftop unit
SCBAself-contained breathing apparatus
SDSsafety data sheet
SPDTsingle-pole, double-throw
SPSTsingle-pole, single-throw
SSTsaturated suction temperature
timperial ton
TDGtransportation of dangerous goods
TDRtime delay relay
TEVthermostatic expansion valve
TXVthermostatic expansion valve
USGUnited States gallons
USGPMUnited States gallons per minute
UVultraviolet
Vvolt
VAvolt-ampere
VACvolts alternating current
VAVvariable air volume
VDCvolt direct current
VFDvariable frequency drive
VRFvariable refrigerant flow
Wwatt
w.c.water column
WHMISWorkplace Hazardous Information Management System
µmmicron
°Cdegree Celsius
°Fdegree Fahrenheit
Aampere
A/Cair conditioning / air conditioner
ABalkylbenzene
ACalternating current
AHJauthority having jurisdiction
ANT.anticipator
ASHRAEAmerican Society of Heating, Refrigerating and Air-Conditioning Engineers
BTUBritish thermal unit
BTU/lbBritish thermal units per pound
BtuhBritish thermal units per hour
C.E.C.Canadian Electrical Code
CFHcubic feet per hour
CFMcubic feet per minute
cmcentimetre
COPcoefficient of performance
CPRcrankcase pressure regulator
CRACcomputer room air conditioning
CSACanadian Standards Association
CSIRcapacitor start / induction run rotor
dBAA-weighted decibel
DHUMdehumidifier
DIPdual in-line package
DPDTdouble-pole, double-throw
DTFDdefrost terminate fan delay
DXdirect expansion
ECMelectronic control module
EEVelectronic expansion valve
EPRevaporator pressure regulator
ERVenergy recovery ventilation
EXVelectric expansion valve
FLAfull load amperage
fpmfeet per minute
ft.foot
GFCIground fault circuit interrupter
GNDground
Hgmercury
hphorsepower
HRVheat recovery ventilator
HVACheating, ventilation and air conditioning
HVAC/Rheating, ventilation, air conditioning and refrigeration
Hzhertz
IDinside diameter
IMDGInternational Maritime Dangerous Goods
in²square inch
inHginches of mercury
inHg vacinches of mercury vacuum
IRinfrared
ISOInternational Organization for Standardization
JOHSCJoint Occupational Health and Safety Committee
kPaGkilopascal gauge
lb.pound
LEDlight-emitting diode
LLSVliquid line solenoid valve
LOTOlock-out and tag-out
LPSlow pressure switch
LRlong radius
mmmillimetre
MOmineral oil
NCnormally closed
NOnormally open
NTCnegative temperature coefficient
OAToutside air temperature
ODoutside diameter
OFCoil failure control
OFMoutdoor fan motor
OHSOccupational Health and Safety
ORDopen on rise of differential
ORIopen on rise of inlet
OROopen on rise of outlet
P/Epressure enthalpy
P/Tpressure temperature
POEpolyolester
PPEpersonal protective equipment
PSCpermanent split capacitor
psipounds per square inch
psiapounds per square inch absolute
psigpounds per square inch gauge
PTACpackaged terminal air conditioner
PTCpositive temperature coefficient
R / °RRankin scale
R.H.relative humidity
rpmrevolutions per minute
RTUrooftop unit
SCBAself-contained breathing apparatus
SDSsafety data sheet
SPDTsingle-pole, double-throw
SPSTsingle-pole, single-throw
SSTsaturated suction temperature
timperial ton
TDGtransportation of dangerous goods
TDRtime delay relay
TEVthermostatic expansion valve
TXVthermostatic expansion valve
USGUnited States gallons
USGPMUnited States gallons per minute
UVultraviolet
Vvolt
VAvolt-ampere
VACvolts alternating current
VAVvariable air volume
VDCvolt direct current
VFDvariable frequency drive
VRFvariable refrigerant flow
Wwatt
w.c.water column
WHMISWorkplace Hazardous Information Management System
µmmicron