Use fractions rather than percentage numbers. U and R must use reciprocal compatible units; 1 in²=1/144 ft².
- Q = gross area × free-area fraction × velocity
- Gross area = Q / (velocity × free-area fraction)
- Outdoor-air fraction = outdoor CFM / total CFM
- U = 1/R; heat rate = U × area × ΔT
- 1Calculate the effective open area, accounting for grille free area.
- 2Use total flow as the denominator for a supply-air percentage.
A 12×12 in. grille is 1 ft² gross. At 60% free area and 500 ft/min, flow=1×0.60×500=300 CFM.
- Do not use gross grille area as if it were completely open.
- Thermal R and electrical resistance use different units and contexts.
Pass Your Red Seal’s lessons and practice are independent study material. Source: Red Seal: formula resources by trade
Try one
A 2 ft² grille is 50% free area. Velocity through the open area is 600 ft/min. Find airflow.