Efficiency, COP and heat rejection

Use one common power or energy unit. COP is a ratio and may exceed 1 because heat is moved, not created.

The formulas
  • η = useful output / input
  • COPcooling = cooling effect / compressor work
  • COPheating = heat delivered / compressor work
  • Heat rejected = cooling effect + compressor work
  • For the same idealized balanceCOPheating = COPcooling + 1
How to do it
  1. 1Write a heat/power balance around the device.
  2. 2Select useful output for the actual mode and divide by input.
Worked example

A cooling unit removes 12 kW while taking 3 kW. Cooling COP = 12/3 = 4; heat rejection = 12 + 3 = 15 kW. Heating COP = 15/3 = 5 if all that heat is useful.

The usual mistakes
  • Heat rejection divided by net refrigeration effect is not the standard cooling COP.
  • Electrical input and motor shaft output are different.

Pass Your Red Seal’s lessons and practice are independent study material. Source: Red Seal: formula resources by trade

Try one

A motor delivers 7.5 kW while drawing 9 kW of real electrical power. Find efficiency.

This topic

The lesson and a worked example
Practice questions in this topic12