Airflow, sensible and total heat

Δh: enthalpy difference in BTU/lb of dry air. 1.08, 4.5 and 4005 are standard-air approximations; actual density and moisture conditions matter.

The formulas
  • Sensible Btuh ≈ 1.08 × CFM × Δ°F
  • Total Btuh ≈ 4.5 × CFM × Δh
  • CFM = area(ft²) × velocity(ft/min)
  • Velocity(ft/min) ≈ 4005√VP(in. w.c.)
How to do it
  1. 1Use temperature difference for sensible load and enthalpy difference for total load.
  2. 2Convert square inches to square feet by dividing by 144.
Worked example

A 1000 CFM air stream with a 20 °F temperature rise carries approximately 1.08 × 1000 × 20 = 21600 Btu/h of sensible heat at standard air conditions.

The usual mistakes
  • Do not multiply gpm by CFM to obtain heat rate.
  • Velocity pressure must be in the units required by the 4005 factor.

Pass Your Red Seal’s lessons and practice are independent study material. Source: Red Seal: formula resources by trade

Try one

At standard-air conditions, 500 CFM warms by 30 °F. Find sensible heat using 1.08.