Gasfitter – Class A Math
Online Red Seal Exam Preparation, built on official standardsMathQuestion 4 of 1070% to goContinue at question 4
10 questions
2 right · 1 wrong · 7 to do- 1Clocking a commercial meter at 2 psig
- 2Gas input of a 150 BHP boiler
- 3Purging a mechanical room before relighting
- 4The boiler horsepower constant
- 5Boiler output from flow and temperature rise
- 6Air flow through a unit heater
- 7Regulator outlet pressure in psig
- 8Replacing an electric boiler with gas
- 9CO₂ reading at 25% excess air
- 10Expected rotation time on a 2 psig meter
Part 1
2 right · 1 wrong · 7 to do- 1Clocking a commercial meter at 2 psigCFH = (dial ÷ SPR) × 3 600 × PF · Procedural and application
- 2Gas input of a 150 BHP boilerInput = output ÷ efficiency · Procedural and application
- 3Purging a mechanical room before relightingPurge time = volume × air changes ÷ SCFM · Critical thinking
- 4The boiler horsepower constantOutput = BHP × 33 500 · Knowledge and recall
- 5Boiler output from flow and temperature riseOutput = ΔT × 8.33 × 60 × USGPM · Procedural and application
- 6Air flow through a unit heaterCFM = (Btuh × E) ÷ (1.08 × ΔT) · Procedural and application
- 7Regulator outlet pressure in psigConversion · Procedural and application
- 8Replacing an electric boiler with gasBTU per 1 000 W = 3.414 · Procedural and application
- 9CO₂ reading at 25% excess air% CO₂ = stoich CO₂ ÷ (1 + % excess air ÷ 100) · Procedural and application
- 10Expected rotation time on a 2 psig meterSeconds per rotation · Critical thinking