Gas meter timing and pressure correction
Use consistent pressure units and the specified base condition. The simple pressure-only model assumes unchanged temperature and compressibility.
- Volume rate = dial volume × 3600 / seconds per revolution × pressure factor
- Pressure factor = (atmospheric + gauge pressure) / base absolute pressure
- Input heat rate = corrected volume rate × stated heating value
- 1Time a stated meter volume and convert to volume per hour.
- 2Correct to the stated base pressure using absolute pressure.
- 3Apply heating value only when an energy input is requested.
A 1 ft³ dial turning in 36 s gives 100 ft³/h uncorrected. At pressure factor 1.1 the corrected rate is 110 ft³/h.
- Gauge pressure alone cannot be used as the numerator of an absolute-pressure ratio.
- Real billing/precision measurement may also compensate temperature and compressibility.
Pass Your Red Seal’s lessons and practice are independent study material. Source: Red Seal: formula resources by trade
Try one
A 2 ft³ dial turns once in 72 s. At pressure factor 1.0, find gas rate.