Instrumentation and Control Technician formula sheet and conversions
MathReference139 formulas · 52 conversions · 58 acronyms
On the exam
- Official formula sheet
- None for this trade
- Conversions
- Not given: learn them
- Acronyms
- You get the list
- Calculator
- The same calculator as here
On the exam
Formula sheetNone for this trade
CalculatorThe same as here
Formulas
139 formulasThe Red Seal Program does not publish a formula sheet for this trade, so these are the formulas its math lessons use.
V = I × R
I = V / R
R = V / I
Rₜ = R₁ + R₂ + …
Vₜ = V₁ + V₂ + …
1/Rₜ = 1/R₁ + 1/R₂ + …
Rₜ = R₁R₂ / (R₁ + R₂) (two branches)
Rₜ = R / n (n equal branches)
ΣI entering = ΣI leaving
ΣV around a closed loop = 0
P = VI = I²R = V²/R (DC resistive load)
E = P × t
1 hp ≈ 746 W
Vout = Vin × R₂ / (R₁ + R₂)
I₁ = Iₜ × R₂ / (R₁ + R₂) (two parallel branches)
SeriesRₜ = R₁ + R₂ + … + Rₙ
Parallel1/Rₜ = 1/R₁ + 1/R₂ + … + 1/Rₙ
I = V/R
Unloaded dividerVout = Vin × R₂/(R₁ + R₂)
S₁φ = VI
P₁φ = VI × PF
S₃φ = √3 × Vline × Iline
P₃φ = √3 × Vline × Iline × PF = 3 × Vphase × Iphase × PF
PF = P/S = cos φ (sinusoidal voltage and current)
Np/Ns = Vp/Vs = Is/Ip (ideal transformer)
WyeVline = √3 × Vphase; Iline = Iphase
DeltaIline = √3 × Iphase; Vline = Vphase
Isc ≈ Irated / (Z% / 100)
Ns = 120f / p
f = pNs / 120
Slip (%) = (Ns − Nr) / Ns × 100
Vrms = Vpeak / √2
Vpeak = √2 × Vrms
Full-wave rectified average = 2 × Vpeak / π ≈ 0.6366 × Vpeak
x = (PV − LRV) / (URV − LRV)
mA = 4 + 16x
PV = LRV + ((mA − 4) / 16) × (URV − LRV)
Q/Qmax = √(ΔP/ΔPmax)
ΔP = ΔPmax × (Q/Qmax)²
Flow-linear mA = 4 + 16√(ΔP/ΔPmax)
P = ρgh
P(kPa) = 9.80665 × SG × h(m)
P(psi) ≈ h(ft) × SG / 2.31
ΔP = ρprocess × g × h − ρreference × g × Href
LRV = ΔP at minimum level
URV = ΔP at maximum level
Span = URV − LRV
Span = URV − LRV
Error = indicated − reference
Error (% span) = error / |span| × 100
Tolerance = specified % × |span| / 100
R ≈ R₀(1 + αT)
T ≈ (R/R₀ − 1) / α
Two-wire measured resistance = sensor resistance + both lead resistances
Kp = 100 / PB%
Δoutput% = Kp × Δerror%
3–15 psi signal = 3 + 12 × fraction of span
Q = A × v
A₁v₁ = A₂v₂ (constant-density steady flow)
ṁ = ρ × Q
F = P × A
A = πd²/4
Retracting annular area = π(D² − d²)/4
°F = 1.8 × °C + 32
°C = (°F − 32) / 1.8
K = °C + 273.15
Δ°F = 1.8 × Δ°C
1 US gal = 3.785411784 L; 1 Imperial gal = 4.54609 L
RectangleA = LW; perimeter = 2(L+W)
TriangleA = bh/2; perimeter = a+b+c
CircleA = πr² = πd²/4; C = πd
BoxV = LWH
CylinderV = πr²h
SphereV = 4πr³/3
Cone or pyramidV = base area × h/3
Triangular wedgeV = LWH/2
1 m³ = 1000 L
Cylinder side = 2πrh
Cylinder with one end = 2πrh + πr²
Closed cylinder = 2πrh + 2πr²
Closed box = 2(LW + LH + WH)
Open box = LW + 2LH + 2WH
Sphere = 4πr²
Cone lateral area = πrs
Pyramid lateral area = perimeter of base × slant height / 2
c² = a² + b²
sin θ = opposite/hypotenuse
cos θ = adjacent/hypotenuse
tan θ = opposite/adjacent
θ = atan(rise/run)
Offset travel = offset / sin θ
Arc length = πrθ/180 = πdθ/360
Sector pattern angle = 360 × base radius / slant radius
Equivalent formpattern angle = 180 × base diameter / slant radius
Grade (%) = rise/run × 100
Rise = run × unit rise/unit run
Symmetrical roof run = span/2
Rafter line length = √(run² + rise²)
Unit line length (per 12 of run) = √(12² + unit rise²)
ΔL = αL₀ΔT
Final length = L₀ + ΔL
P₁V₁ = P₂V₂ (constant temperature)
V₁/T₁ = V₂/T₂ (constant pressure)
P₁V₁/T₁ = P₂V₂/T₂ (fixed ideal-gas quantity)
Q = mcΔT
Heat rate = ṁcΔT
Btuh ≈ 500 × US gpm × Δ°F (water)
US gpm = Btuh / (500 × Δ°F)
Δ°F = Btuh / (500 × US gpm)
η = useful output / input
COPcooling = cooling effect / compressor work
COPheating = heat delivered / compressor work
Heat rejected = cooling effect + compressor work
For the same idealized balanceCOPheating = COPcooling + 1
Q₂/Q₁ = N₂/N₁
Head₂/Head₁ = (N₂/N₁)²
Power₂/Power₁ ≈ (N₂/N₁)³
D₁N₁ = D₂N₂ (belt drive, no slip)
New quantity = original quantity × scale factor
Scale factor = required yield / original yield
With p% addedfinal = original × (1+p/100)
Baker’s percentage = ingredient mass / flour mass × 100
Xc = 1/(2πfC)
Xl = 2πfL
Series impedance magnitude = √(R² + (Xl−Xc)²)
RC time constant τ = RC
ChargingVc = Vs(1−e−t/τ)
Available loop resistance = (supply voltage − required device voltage − fixed drops) / maximum current
Volume = pulse count / Kfactor
Flow = pulse frequency / Kfactor
Percent span discrepancy = (observed − expected)/span × 100
θ = kI²
k = θcal / Ical²
I = √(θ/k)
θ₂/θ₁ = (I₂/I₁)²
Rseries = ΣR
1/Rparallel = Σ(1/R)
V = IR
P = I²R
Ohm’s law
V = I × R
I = V / R
R = V / I
Resistors in series
Rₜ = R₁ + R₂ + …
Vₜ = V₁ + V₂ + …
Resistors in parallel
1/Rₜ = 1/R₁ + 1/R₂ + …
Rₜ = R₁R₂ / (R₁ + R₂) (two branches)
Rₜ = R / n (n equal branches)
Kirchhoff’s current and voltage laws
ΣI entering = ΣI leaving
ΣV around a closed loop = 0
Electrical power and energy
P = VI = I²R = V²/R (DC resistive load)
E = P × t
1 hp ≈ 746 W
Voltage and current dividers
Vout = Vin × R₂ / (R₁ + R₂)
I₁ = Iₜ × R₂ / (R₁ + R₂) (two parallel branches)
Reading circuit diagrams and calculating values
SeriesRₜ = R₁ + R₂ + … + Rₙ
Parallel1/Rₜ = 1/R₁ + 1/R₂ + … + 1/Rₙ
I = V/R
Unloaded dividerVout = Vin × R₂/(R₁ + R₂)
AC power, power factor and three-phase loads
S₁φ = VI
P₁φ = VI × PF
S₃φ = √3 × Vline × Iline
P₃φ = √3 × Vline × Iline × PF = 3 × Vphase × Iphase × PF
PF = P/S = cos φ (sinusoidal voltage and current)
Transformers, wye/delta and fault-current estimates
Np/Ns = Vp/Vs = Is/Ip (ideal transformer)
WyeVline = √3 × Vphase; Iline = Iphase
DeltaIline = √3 × Iphase; Vline = Vphase
Isc ≈ Irated / (Z% / 100)
Motor speed, frequency and slip
Ns = 120f / p
f = pNs / 120
Slip (%) = (Ns − Nr) / Ns × 100
RMS, peak and rectified average
Vrms = Vpeak / √2
Vpeak = √2 × Vrms
Full-wave rectified average = 2 × Vpeak / π ≈ 0.6366 × Vpeak
4–20 mA scaling and reverse calculation
x = (PV − LRV) / (URV − LRV)
mA = 4 + 16x
PV = LRV + ((mA − 4) / 16) × (URV − LRV)
Differential-pressure flow and square-root extraction
Q/Qmax = √(ΔP/ΔPmax)
ΔP = ΔPmax × (Q/Qmax)²
Flow-linear mA = 4 + 16√(ΔP/ΔPmax)
Hydrostatic head, density and specific gravity
P = ρgh
P(kPa) = 9.80665 × SG × h(m)
P(psi) ≈ h(ft) × SG / 2.31
DP level: wet legs, dry legs and zero shift
ΔP = ρprocess × g × h − ρreference × g × Href
LRV = ΔP at minimum level
URV = ΔP at maximum level
Span = URV − LRV
Calibration error, span and accuracy
Span = URV − LRV
Error = indicated − reference
Error (% span) = error / |span| × 100
Tolerance = specified % × |span| / 100
RTDs, lead resistance and temperature
R ≈ R₀(1 + αT)
T ≈ (R/R₀ − 1) / α
Two-wire measured resistance = sensor resistance + both lead resistances
Control gain, proportional band and valve signals
Kp = 100 / PB%
Δoutput% = Kp × Δerror%
3–15 psi signal = 3 + 12 × fraction of span
Flow, velocity and mass flow
Q = A × v
A₁v₁ = A₂v₂ (constant-density steady flow)
ṁ = ρ × Q
Pressure, force and piston area
F = P × A
A = πd²/4
Retracting annular area = π(D² − d²)/4
Temperature and unit conversion
°F = 1.8 × °C + 32
°C = (°F − 32) / 1.8
K = °C + 273.15
Δ°F = 1.8 × Δ°C
1 US gal = 3.785411784 L; 1 Imperial gal = 4.54609 L
Areas, perimeter and circumference
RectangleA = LW; perimeter = 2(L+W)
TriangleA = bh/2; perimeter = a+b+c
CircleA = πr² = πd²/4; C = πd
Volumes, capacity and material quantities
BoxV = LWH
CylinderV = πr²h
SphereV = 4πr³/3
Cone or pyramidV = base area × h/3
Triangular wedgeV = LWH/2
1 m³ = 1000 L
Surface area of vessels and insulation
Cylinder side = 2πrh
Cylinder with one end = 2πrh + πr²
Closed cylinder = 2πrh + 2πr²
Closed box = 2(LW + LH + WH)
Open box = LW + 2LH + 2WH
Sphere = 4πr²
Cone lateral area = πrs
Pyramid lateral area = perimeter of base × slant height / 2
Pythagoras, trigonometry and offsets
c² = a² + b²
sin θ = opposite/hypotenuse
cos θ = adjacent/hypotenuse
tan θ = opposite/adjacent
θ = atan(rise/run)
Offset travel = offset / sin θ
Arc lengths and developed patterns
Arc length = πrθ/180 = πdθ/360
Sector pattern angle = 360 × base radius / slant radius
Equivalent formpattern angle = 180 × base diameter / slant radius
Grade, roof rise and run
Grade (%) = rise/run × 100
Rise = run × unit rise/unit run
Symmetrical roof run = span/2
Rafter line length = √(run² + rise²)
Unit line length (per 12 of run) = √(12² + unit rise²)
Thermal expansion and contraction
ΔL = αL₀ΔT
Final length = L₀ + ΔL
Boyle’s, Charles’ and combined gas laws
P₁V₁ = P₂V₂ (constant temperature)
V₁/T₁ = V₂/T₂ (constant pressure)
P₁V₁/T₁ = P₂V₂/T₂ (fixed ideal-gas quantity)
Sensible heat, hydronic flow and capacity
Q = mcΔT
Heat rate = ṁcΔT
Btuh ≈ 500 × US gpm × Δ°F (water)
US gpm = Btuh / (500 × Δ°F)
Δ°F = Btuh / (500 × US gpm)
Efficiency, COP and heat rejection
η = useful output / input
COPcooling = cooling effect / compressor work
COPheating = heat delivered / compressor work
Heat rejected = cooling effect + compressor work
For the same idealized balanceCOPheating = COPcooling + 1
Fan, pump and pulley ratios
Q₂/Q₁ = N₂/N₁
Head₂/Head₁ = (N₂/N₁)²
Power₂/Power₁ ≈ (N₂/N₁)³
D₁N₁ = D₂N₂ (belt drive, no slip)
Percentages, recipe scaling and quantities
New quantity = original quantity × scale factor
Scale factor = required yield / original yield
With p% addedfinal = original × (1+p/100)
Baker’s percentage = ingredient mass / flour mass × 100
Reactance, impedance and RC timing
Xc = 1/(2πfC)
Xl = 2πfL
Series impedance magnitude = √(R² + (Xl−Xc)²)
RC time constant τ = RC
ChargingVc = Vs(1−e−t/τ)
Loop loading, pulse totals and proof checks
Available loop resistance = (supply voltage − required device voltage − fixed drops) / maximum current
Volume = pulse count / Kfactor
Flow = pulse frequency / Kfactor
Percent span discrepancy = (observed − expected)/span × 100
Square-law instrument scales
θ = kI²
k = θcal / Ical²
I = √(θ/k)
θ₂/θ₁ = (I₂/I₁)²
Series and parallel circuit workshop
Rseries = ΣR
1/Rparallel = Σ(1/R)
V = IR
P = I²R
On the exam
ConversionsNot given: learn them
Conversions
52 conversions1 psi6.895 kPa
1 kPa0.1450 psi
1 bar100 kPa
1 bar14.50 psi
1 atm101.3 kPa
1 atm14.70 psi
1 in w.c.249.1 Pa
1 ft of water0.4335 psi
1 in Hg3.386 kPa
1 lbf4.448 N
1 kN224.8 lbf
°C to °F× 1.8, then + 32
°F to °C− 32, then ÷ 1.8
°C to K+ 273.15
A difference of 1 °C1.8 °F
Water freezes0 °C = 32 °F
Water boils (sea level)100 °C = 212 °F
1 L/s60 L/min
1 L/s3.6 m³/h
1 L/s15.85 US gpm
1 L/s13.20 imp gpm
1 US gpm3.785 L/min
1 imp gpm4.546 L/min
1 cfm0.4719 L/s
1 cfm1.699 m³/h
1 m³/h0.5886 cfm
Power (W)V × A
1 kW1 000 W
1 kVA1 000 VA
1 hp746 W
1 mA0.001 A
1 mV0.001 V
1 kΩ1 000 Ω
1 MΩ1 000 000 Ω
1 kWh1 kW for 1 hour
1 in25.4 mm
1 ft304.8 mm
1 ft0.3048 m
1 yd0.9144 m
1 m3.281 ft
1 m39.37 in
1 km0.6214 mi
1 mi1.609 km
Water1 000 kg/m³ = 1 kg/L
Water62.4 lb/ft³
Water8.34 lb per US gal
Water10.0 lb per imp gal
Steel7 850 kg/m³ = 490 lb/ft³
Steel plate7.85 kg per m² per mm
Concrete2 400 kg/m³ = 150 lb/ft³
1 kg/m³0.06243 lb/ft³
1 lb/ft³16.02 kg/m³
Pressure and force
1 psi6.895 kPa
1 kPa0.1450 psi
1 bar100 kPa
1 bar14.50 psi
1 atm101.3 kPa
1 atm14.70 psi
1 in w.c.249.1 Pa
1 ft of water0.4335 psi
1 in Hg3.386 kPa
1 lbf4.448 N
1 kN224.8 lbf
Temperature
°C to °F× 1.8, then + 32
°F to °C− 32, then ÷ 1.8
°C to K+ 273.15
A difference of 1 °C1.8 °F
Water freezes0 °C = 32 °F
Water boils (sea level)100 °C = 212 °F
Flow
1 L/s60 L/min
1 L/s3.6 m³/h
1 L/s15.85 US gpm
1 L/s13.20 imp gpm
1 US gpm3.785 L/min
1 imp gpm4.546 L/min
1 cfm0.4719 L/s
1 cfm1.699 m³/h
1 m³/h0.5886 cfm
Electrical
Power (W)V × A
1 kW1 000 W
1 kVA1 000 VA
1 hp746 W
1 mA0.001 A
1 mV0.001 V
1 kΩ1 000 Ω
1 MΩ1 000 000 Ω
1 kWh1 kW for 1 hour
Length
1 in25.4 mm
1 ft304.8 mm
1 ft0.3048 m
1 yd0.9144 m
1 m3.281 ft
1 m39.37 in
1 km0.6214 mi
1 mi1.609 km
Density and unit mass
Water1 000 kg/m³ = 1 kg/L
Water62.4 lb/ft³
Water8.34 lb per US gal
Water10.0 lb per imp gal
Steel7 850 kg/m³ = 490 lb/ft³
Steel plate7.85 kg per m² per mm
Concrete2 400 kg/m³ = 150 lb/ft³
1 kg/m³0.06243 lb/ft³
1 lb/ft³16.02 kg/m³
On the exam
AcronymsYou get the list
Acronyms
58 acronymsThe following acronyms used in this trade may be on its Red Seal exam. They will also be provided with the exam sitting. The official list (PDF)
A/Danalogue to digital
ASCIIAmerican Standard Code for Information Interchange
CSACanadian Standards Association
Cvvalve flow coefficient
D/Adigital to analogue
DCSdistributed control system
DPdifferential pressure
DPDdouble-polled double throw
E/Ielectrical and instrumentation
EEPROMelectronically erasable programmable read-only memory
EMIelectromagnetic interference
ESDemergency shutdown device
FCfailed close
FOfailed open
HARThighway addressable remote transducer
HMIhuman machine interface
I/Oinput/output
I/Pcurrent-to-pneumatic
ISAInternational Society of Automation
LELlower explosive limit
LRVlower range value
LVDTlinear variable displacement transformer
MAmanual/automatic
MACmedia access control
MCCmotor control centre
NCnormally closed
NEMANational Electrical Manufacturers Association
NOnormally open
OHSAOccupational health and Safety Act
P/Ipiping and instrumentation
P/IDprocess and instrumentation diagram
PBproportional band
PCSprocess control system
PIDproportional integral derivative
PLCprogrammable logic controller
PSSprocess safety system
PVprocess variable
QA/QCquality assurance and quality control
RAMrandom access memory
RFIradio frequency interference
RRFrisk reduction factor
RTDresistance temperature detector
RTUremote terminal unit
SACstand-alone controller
SAMAScientific Apparatus Makers Association
SCADAsupervisory control and data acquisition
SCBAself-contained breathing apparatus
SDSsafety data sheet
SFPsmall form-factor pluggable
SILsafety integrity level
SISsafety instrumented system
SPset point
SPDTsingle-pole double throw
TCP/IPtransmission control protocol/Internet protocol
UPSuninterruptable power supply
URVupper range value
Vsdvariable speed drive
WHMISWorkplace Hazardous Materials Information System
A/Danalogue to digital
ASCIIAmerican Standard Code for Information Interchange
CSACanadian Standards Association
Cvvalve flow coefficient
D/Adigital to analogue
DCSdistributed control system
DPdifferential pressure
DPDdouble-polled double throw
E/Ielectrical and instrumentation
EEPROMelectronically erasable programmable read-only memory
EMIelectromagnetic interference
ESDemergency shutdown device
FCfailed close
FOfailed open
HARThighway addressable remote transducer
HMIhuman machine interface
I/Oinput/output
I/Pcurrent-to-pneumatic
ISAInternational Society of Automation
LELlower explosive limit
LRVlower range value
LVDTlinear variable displacement transformer
MAmanual/automatic
MACmedia access control
MCCmotor control centre
NCnormally closed
NEMANational Electrical Manufacturers Association
NOnormally open
OHSAOccupational health and Safety Act
P/Ipiping and instrumentation
P/IDprocess and instrumentation diagram
PBproportional band
PCSprocess control system
PIDproportional integral derivative
PLCprogrammable logic controller
PSSprocess safety system
PVprocess variable
QA/QCquality assurance and quality control
RAMrandom access memory
RFIradio frequency interference
RRFrisk reduction factor
RTDresistance temperature detector
RTUremote terminal unit
SACstand-alone controller
SAMAScientific Apparatus Makers Association
SCADAsupervisory control and data acquisition
SCBAself-contained breathing apparatus
SDSsafety data sheet
SFPsmall form-factor pluggable
SILsafety integrity level
SISsafety instrumented system
SPset point
SPDTsingle-pole double throw
TCP/IPtransmission control protocol/Internet protocol
UPSuninterruptable power supply
URVupper range value
Vsdvariable speed drive
WHMISWorkplace Hazardous Materials Information System