Differential-pressure flow and square-root extraction
Q: flow rate · ΔP: differential pressure. Fixed primary element, constant density and established turbulent-flow calibration are assumed; zero-based DP range.
- Q/Qmax = √(ΔP/ΔPmax)
- ΔP = ΔPmax × (Q/Qmax)²
- Flow-linear mA = 4 + 16√(ΔP/ΔPmax)
- 1Normalize DP to its full-scale value.
- 2Apply the square root exactly once, in the configured transmitter or controller.
- 3Distinguish a DP-linear signal from a flow-linear signal.
At 25 kPa on a 0–100 kPa DP range, flow is √0.25=50% of maximum. DP-linear output is 8 mA; flow-linear output is 12 mA.
- 50% flow corresponds to 25% DP.
- Applying square root twice produces a high indication.
- Density changes and low-flow cutoff require the configured compensation model.
kPa
kPa
100 × √(25 / 100). Constant density, zero-based DP range, no low-flow cutoff.50 % flow
Pass Your Red Seal’s lessons and practice are independent study material. Source: Yokogawa: square-root extraction
Try one
An orifice is calibrated for 100 m³/h at 40 kPa DP. At 10 kPa, what is the flow under the same density conditions?
This topic
The lesson and a worked example
Practice questions in this topic12
Mixed practice
Every math topicKeys this topic uses
- x²Squares a number
- 2ndFx²Takes a square root
- ()Works the part in brackets first
- ALPHA=Types ANS, the last answer