Q: flow rate · ΔP: differential pressure. Fixed primary element, constant density and established turbulent-flow calibration are assumed; zero-based DP range.

The formulas
  • Q/Qmax = √(ΔP/ΔPmax)
  • ΔP = ΔPmax × (Q/Qmax)²
  • Flow-linear mA = 4 + 16√(ΔP/ΔPmax)
How to do it
  1. 1Normalize DP to its full-scale value.
  2. 2Apply the square root exactly once, in the configured transmitter or controller.
  3. 3Distinguish a DP-linear signal from a flow-linear signal.
Worked example

At 25 kPa on a 0–100 kPa DP range, flow is √0.25=50% of maximum. DP-linear output is 8 mA; flow-linear output is 12 mA.

The usual mistakes
  • 50% flow corresponds to 25% DP.
  • Applying square root twice produces a high indication.
  • Density changes and low-flow cutoff require the configured compensation model.
Check it with your own values
kPa
kPa
Working

100 × √(25 / 100). Constant density, zero-based DP range, no low-flow cutoff.50 % flow

Pass Your Red Seal’s lessons and practice are independent study material. Source: Yokogawa: square-root extraction

Try one

An orifice is calibrated for 100 m³/h at 40 kPa DP. At 10 kPa, what is the flow under the same density conditions?

This topic

The lesson and a worked example
Practice questions in this topic12
Mixed practiceEvery math topic

Mixed practice

Every math topic

Keys this topic uses

  • x²Squares a number
  • 2ndFx²Takes a square root
  • ()Works the part in brackets first
  • ALPHA=Types ANS, the last answer

Calculator skill: squares and square roots

Topic practice2 questions · 0 done