h: process height above the HP connection · Href: fixed LP reference column. Simplified arrangement: transmitter at lower tap, constant reference density, no other seal-head offsets.

The formulas
  • ΔP = ρprocess × g × h − ρreference × g × Href
  • LRV = ΔP at minimum level
  • URV = ΔP at maximum level
  • Span = URV − LRV
How to do it
  1. 1Draw both pressure paths to the transmitter and calculate the pressure at each port.
  2. 2Subtract LP from HP at empty and full. Do not discard a negative LRV.
  3. 3Scale the resulting DP interval to 4–20 mA.
Worked example

For a 2 m water range with a 3 m water wet leg: LRV=−29.42 kPa; URV=19.61−29.42=−9.81 kPa; span=19.61 kPa. Mid-level gives 12 mA.

The usual mistakes
  • A steam-main drip leg is not the same thing as a DP reference wet leg.
  • Reference density and seal elevation can shift zero without changing the process span.

Pass Your Red Seal’s lessons and practice are independent study material. Source: Yokogawa: DP level and temperature effects

Try one

A DP transmitter at the lower tap measures 0–2 m of water against a fixed 3 m water wet leg. Use 9.81 kPa/m. What is its LRV?