MathOnline Red Seal Exam Preparation, built on official standards
MathDP level: wet legs, dry legs and zero shiftInstrumentationSee study access
DP level: wet legs, dry legs and zero shift
h: process height above the HP connection · Href: fixed LP reference column. Simplified arrangement: transmitter at lower tap, constant reference density, no other seal-head offsets.
- ΔP = ρprocess × g × h − ρreference × g × Href
- LRV = ΔP at minimum level
- URV = ΔP at maximum level
- Span = URV − LRV
- 1Draw both pressure paths to the transmitter and calculate the pressure at each port.
- 2Subtract LP from HP at empty and full. Do not discard a negative LRV.
- 3Scale the resulting DP interval to 4–20 mA.
For a 2 m water range with a 3 m water wet leg: LRV=−29.42 kPa; URV=19.61−29.42=−9.81 kPa; span=19.61 kPa. Mid-level gives 12 mA.
- A steam-main drip leg is not the same thing as a DP reference wet leg.
- Reference density and seal elevation can shift zero without changing the process span.
Pass Your Red Seal’s lessons and practice are independent study material. Source: Yokogawa: DP level and temperature effects
Try one
A DP transmitter at the lower tap measures 0–2 m of water against a fixed 3 m water wet leg. Use 9.81 kPa/m. What is its LRV?
This topic
The lesson and a worked example
Practice questions in this topic12
Mixed practice
Every math topicKeys this topic uses