MathOnline Red Seal Exam Preparation, built on official standards
MathCalibration error, span and accuracyInstrumentationSee study access
Calibration error, span and accuracy
Use the stated accuracy basis: span, upper range limit, reading or a combined specification are not interchangeable.
- Span = URV − LRV
- Error = indicated − reference
- Error (% span) = error / |span| × 100
- Tolerance = specified % × |span| / 100
- 1Record reference and indication at the same point.
- 2Calculate signed error, then compare absolute error with tolerance.
- 3Check several upscale/downscale points to distinguish offset, gain and hysteresis.
A 0–400 kPa transmitter indicates 202 kPa at a 200 kPa reference. Error = +2 kPa = +0.5% of span. At ±0.25% of span tolerance (±1 kPa), it fails this point.
- A correct digital PV with an incorrect loop signal points to a different part of the measurement chain than a sensor error.
Pass Your Red Seal’s lessons and practice are independent study material. Source: Yokogawa: square-root extraction
Try one
A −50 to 150 °C transmitter reads 51 °C at a 50 °C reference. What is the error as a percentage of span?
This topic
The lesson and a worked example
Practice questions in this topic12
Mixed practice
Every math topicKeys this topic uses
- ()Works the part in brackets first
- ALPHA=Types ANS, the last answer