4–20 mA scaling and reverse calculation
PV: process value · LRV/URV: values assigned to 4/20 mA · x: fraction of span. A linear signal is assumed.
- x = (PV − LRV) / (URV − LRV)
- mA = 4 + 16x
- PV = LRV + ((mA − 4) / 16) × (URV − LRV)
- 1Subtract the lower range value, then divide by span.
- 2Scale the fraction over 16 mA and add the 4 mA live zero.
- 3Reverse the operation to check the original engineering value.
For −50 to 150 °C at 70 °C: x=(70+50)/200=0.60; output=4+16×0.60=13.6 mA. Reverse: −50+(9.6/16)×200=70 °C.
- The signal span is 16 mA, not 20 mA.
- A nonzero or negative LRV must be included.
- Do not take the square root of mA directly.
engineering units
engineering units
engineering units
4 + 16 × (70 − (-50)) / (150 − (-50)). Linear output.13.6 mA
Pass Your Red Seal’s lessons and practice are independent study material. Source: Yokogawa: square-root extraction
Try one
A linear transmitter spans 0–200 kPa. What output corresponds to 50 kPa?