MathOnline Red Seal Exam Preparation, built on official standards
MathLoop loading, pulse totals and proof checksInstrumentationSee study access
Loop loading, pulse totals and proof checks
Kfactor: pulses per unit volume. Use current in amperes and include every series burden. The device’s required minimum voltage comes from its applicable specification.
- Available loop resistance = (supply voltage − required device voltage − fixed drops) / maximum current
- Volume = pulse count / Kfactor
- Flow = pulse frequency / Kfactor
- Percent span discrepancy = (observed − expected)/span × 100
- 1Separate sensor value, digital PV, analogue signal and controller indication.
- 2Check a known physical input at each stage so the first disagreement is located.
A 24 V loop with 12 V required by the device and 2 V fixed drops has 10 V available. At 20 mA, total allowable resistance is 10/0.020=500 Ω.
- Adding a 250 Ω resistor to an already loaded loop can exceed available voltage.
- A pulse factor in pulses/L is divided into pulse count; L/pulse would be multiplied.
Pass Your Red Seal’s lessons and practice are independent study material. Source: Yokogawa: square-root extraction
Try one
A 24 V supply must leave 12 V at a transmitter at 20 mA. With no other fixed drops, what maximum series resistance is available?
This topic
The lesson and a worked example
Practice questions in this topic12
Mixed practice
Every math topicKeys this topic uses
- ()Works the part in brackets first
- ALPHA=Types ANS, the last answer