Pass Your Red Seal
MathOnline Red Seal Exam Preparation, built on official standards
MathControl gain, proportional band and valve signalsInstrumentationSee study access
All math

Control gain, proportional band and valve signals

Kp: dimensionless proportional gain when input/output use percent of span · PB: proportional band. Sign depends on the configured controller action.

The formulas
  • Kp = 100 / PB%
  • Δoutput% = Kp × Δerror%
  • 3–15 psi signal = 3 + 12 × fraction of span
How to do it
  1. 1Normalize the input error to percent of input span.
  2. 2Apply the proportional gain and action sign; add the stated bias if finding absolute output.
  3. 3Clamp only when a stated output limit is reached.
Worked example

With PB = 50%, Kp = 2. An error change of +3 percentage points of span produces an output change of +6 percentage points for the stated positive-action convention. From a 40% bias, the output becomes 46%.

The usual mistakes
  • Controller algorithms and integral-time conventions differ by manufacturer.
  • An I/P converter’s signal span is 12 psi, not 15 psi.

Pass Your Red Seal’s lessons and practice are independent study material. Source: Yokogawa: square-root extraction

Try one

What proportional gain corresponds to a 25% proportional band?

This topic

The lesson and a worked example
Practice questions in this topic12
Mixed practiceEvery math topic

Mixed practice

Every math topic

Keys this topic uses

  • 2ndF1Percent, the second job of 1
  • ALPHA=Types ANS, the last answer

Calculator skill: percentages

Topic practice2 questions · 0 done