Control gain, proportional band and valve signals
Kp: dimensionless proportional gain when input/output use percent of span · PB: proportional band. Sign depends on the configured controller action.
- Kp = 100 / PB%
- Δoutput% = Kp × Δerror%
- 3–15 psi signal = 3 + 12 × fraction of span
- 1Normalize the input error to percent of input span.
- 2Apply the proportional gain and action sign; add the stated bias if finding absolute output.
- 3Clamp only when a stated output limit is reached.
With PB = 50%, Kp = 2. An error change of +3 percentage points of span produces an output change of +6 percentage points for the stated positive-action convention. From a 40% bias, the output becomes 46%.
- Controller algorithms and integral-time conventions differ by manufacturer.
- An I/P converter’s signal span is 12 psi, not 15 psi.
Pass Your Red Seal’s lessons and practice are independent study material. Source: Yokogawa: square-root extraction
Try one
What proportional gain corresponds to a 25% proportional band?