Identify the exact model, output/protocol suffix, sensor range and configured transfer function before interpreting a reading.

THE FORMULAS

  • Linear DP: mA = 4 + 16 × DP fraction
  • Flow-linear: mA = 4 + 16 × √DP fraction
  • Error = measured output − calculated output

HOW TO DO IT

  1. Record model, sensor input, units, range, damping and linear/square-root settings at both transmitter and host.
  2. Compare applied reference, digital PV, loop current and host engineering value in sequence.
  3. For a temperature input verify sensor type and lead configuration; for DP verify process connections and reference legs.
  4. Record as-found and as-left results using the applicable manufacturer procedure.

Worked example

At 25% applied DP, a DP-linear loop should read 8 mA and a flow-linear loop 12 mA. A controller that roots an already flow-linear signal displays 70.71% instead of 50% flow.

THE USUAL MISTAKES

  • A digital PV error and an analogue output error require different checks.
  • Manufacturer-specific settings and safety procedures depend on the model/protocol; do not assume an entire product family has identical options.

SOURCES AND FURTHER READING

Pass Your Red Seal’s lessons and practice are independent study material. Manufacturer topics extend trade learning; they are not a claim about the content of an official exam.

TRY ONE · FREE

A Yokogawa DP transmitter is correctly configured for flow-linear output. At 25% calibrated DP, what should its loop signal be?