MathOnline Red Seal Exam Preparation, built on official standards
Construction Electrician formula sheet, conversions and acronyms
MathReference28 formulas · 41 conversions · 81 acronyms
On the exam
- Official formula sheet
- Given at the exam
- Conversions
- Not given: learn them
- Acronyms
- You get the list
- Calculator
- The same calculator as here
On the exam
Formula sheetGiven at the exam
CalculatorThe same as here
Formulas
28 formulasFrom the official Construction Electrician formula sheet. The same sheet is printed for you at the exam.
Current(E) / (R)
Frequency(poles × speed) / (120)
Kilovolt-amperes (balanced three phase)kVA = (Eline × Iline × √3) / 1000
Line current (I line )Iphase × √(3)
Line current (I line )(VA) / (Eline × √(3))
Line voltage (E line )Ephase × √(3)
PowerI2 × R
PowerE × I
Power(E2) / (R)
Power factor(true power) / (apparent power)
Resistance(E2) / (P)
Transformer short-circuit estimateIsc ≈ Irated / (%Z / 100)
Three‑phase powerE × I × √(3) × PF
Total power (P total )Eline × Iline × PF × √(3)
Total power (P total )Ephase × Iphase × PF × 3
Turn ratio(Np) / (Ns) = (Ep) / (Es) = (Is) / (Ip)
Volt‑amperesEline × Iline × √(3)
Volt‑amperesEphase × Iphase × 3
Wattshp × 746
Evoltage
hphorsepower
Icurrent
Ppower
PFpower factor
Rresistance
VAvolt‑ampere
√(3)1.73
π3.14
Formulas
Current(E) / (R)
Frequency(poles × speed) / (120)
Kilovolt-amperes (balanced three phase)kVA = (Eline × Iline × √3) / 1000
Line current (I line )Iphase × √(3)
Line current (I line )(VA) / (Eline × √(3))
Line voltage (E line )Ephase × √(3)
PowerI2 × R
PowerE × I
Power(E2) / (R)
Power factor(true power) / (apparent power)
Resistance(E2) / (P)
Transformer short-circuit estimateIsc ≈ Irated / (%Z / 100)
Three‑phase powerE × I × √(3) × PF
Total power (P total )Eline × Iline × PF × √(3)
Total power (P total )Ephase × Iphase × PF × 3
Turn ratio(Np) / (Ns) = (Ep) / (Es) = (Is) / (Ip)
Volt‑amperesEline × Iline × √(3)
Volt‑amperesEphase × Iphase × 3
Wattshp × 746
Measurement unit abbreviations
Evoltage
hphorsepower
Icurrent
Ppower
PFpower factor
Rresistance
VAvolt‑ampere
Constants
√(3)1.73
π3.14
On the exam
ConversionsNot given: learn them
Conversions
41 conversionsPower (W)V × A
1 kW1 000 W
1 kVA1 000 VA
1 hp746 W
1 mA0.001 A
1 mV0.001 V
1 kΩ1 000 Ω
1 MΩ1 000 000 Ω
1 kWh1 kW for 1 hour
1 hp746 W
1 kW1.341 hp
1 kW3 412 Btu/h
1 Btu/h0.2931 W
1 Btu1.055 kJ
1 ton of refrigeration12 000 Btu/h
1 ton of refrigeration3.517 kW
1 kWh3.6 MJ
1 therm100 000 Btu
1 boiler hp33 475 Btu/h
1 in25.4 mm
1 ft304.8 mm
1 ft0.3048 m
1 yd0.9144 m
1 m3.281 ft
1 m39.37 in
1 km0.6214 mi
1 mi1.609 km
°C to °F× 1.8, then + 32
°F to °C− 32, then ÷ 1.8
°C to K+ 273.15
A difference of 1 °C1.8 °F
Water freezes0 °C = 32 °F
Water boils (sea level)100 °C = 212 °F
1 ft²144 in²
1 ft²0.0929 m²
1 m²10.76 ft²
1 yd²9 ft²
1 yd²0.8361 m²
1 ha10 000 m²
1 ha2.471 acres
1 acre4 047 m²
Electrical
Power (W)V × A
1 kW1 000 W
1 kVA1 000 VA
1 hp746 W
1 mA0.001 A
1 mV0.001 V
1 kΩ1 000 Ω
1 MΩ1 000 000 Ω
1 kWh1 kW for 1 hour
Power and energy
1 hp746 W
1 kW1.341 hp
1 kW3 412 Btu/h
1 Btu/h0.2931 W
1 Btu1.055 kJ
1 ton of refrigeration12 000 Btu/h
1 ton of refrigeration3.517 kW
1 kWh3.6 MJ
1 therm100 000 Btu
1 boiler hp33 475 Btu/h
Length
1 in25.4 mm
1 ft304.8 mm
1 ft0.3048 m
1 yd0.9144 m
1 m3.281 ft
1 m39.37 in
1 km0.6214 mi
1 mi1.609 km
Temperature
°C to °F× 1.8, then + 32
°F to °C− 32, then ÷ 1.8
°C to K+ 273.15
A difference of 1 °C1.8 °F
Water freezes0 °C = 32 °F
Water boils (sea level)100 °C = 212 °F
Area
1 ft²144 in²
1 ft²0.0929 m²
1 m²10.76 ft²
1 yd²9 ft²
1 yd²0.8361 m²
1 ha10 000 m²
1 ha2.471 acres
1 acre4 047 m²
On the exam
AcronymsYou get the list
Acronyms
81 acronymsThe following acronyms used in this trade may be on its Red Seal exam. They will also be provided with the exam sitting. The official list (PDF)
Aampere
ACalternating current
AFCIarc-fault circuit interrupter
Ahampere-hour
ANSIAmerican National Standards Institute
AWGAmerican wire gauge
Catcategory
CATVcommunity antenna television
CFCcommunication flat cable
CO₂carbon dioxide
CRcontrol relay
CSACanadian Standards Association
CTcurrent transformer
DCdirect current
EMTelectrical metallic tubing
ENTelectrical non-metallic tubing
FCCflat conductor cable
FLAfull load amperage
FLCfull load current
FSfloat switch
GFCIground-fault circuit interrupter
HIDhigh intensity discharge
hphorsepower
HRVheat recovery ventilator
HVACheating, ventilation and air conditioning
Hzhertz
I/Oinput/output
ICinsulation contact
IECInternational Electrotechnical Commission
IFRindoor fan relay
in.inch
in.-lb.inch-pound
IPingress protection
IRinterrupting rating
K-ratingKelvin-rating
kcmilthousand circular mil
kgkilogram
kVkilovolt
kVAkilovolt-ampere
kWkilowatt
LEDlight-emitting diode
mmetre
m²square metre
mAmilliampere
MCCmotor control centre
minminute
mLmillilitre
mmmillimetre
mm²square millimetre
N•mnewton-metre
NACENational Association of Corrosion Engineers
NBCNational Building Code
NCnormally closed
NEMANational Electrical Manufacturers Association
NGRneutral grounding resistor
NMDnon-metallic dry
NMWnon-metallic wet
NMWUnon-metallic wet underground
NOnormally open
No.number
O.L.overload
PCBpolychlorinated biphenyl
PIRpassive infrared
PLCprogrammable logic controller
PPEpersonal protective equipment
PSpressure switch
PVCpolyvinyl chloride
°Cdegree Celsius
rpmrotations per minute
RTRCreinforced thermosetting resin conduit
ssecond
SCRsilicon-controlled rectifier
SDSsafety data sheet
SQIMsquirrel-cage induction motor
SWDswitching duty
TCthermocouple
TRtimed relay
UPSuninterrupted power supply
Vvolt
VFDvariable frequency drive
Wwatt
°Cdegree Celsius
Aampere
ACalternating current
AFCIarc-fault circuit interrupter
Ahampere-hour
ANSIAmerican National Standards Institute
AWGAmerican wire gauge
Catcategory
CATVcommunity antenna television
CFCcommunication flat cable
CO₂carbon dioxide
CRcontrol relay
CSACanadian Standards Association
CTcurrent transformer
DCdirect current
EMTelectrical metallic tubing
ENTelectrical non-metallic tubing
FCCflat conductor cable
FLAfull load amperage
FLCfull load current
FSfloat switch
GFCIground-fault circuit interrupter
HIDhigh intensity discharge
hphorsepower
HRVheat recovery ventilator
HVACheating, ventilation and air conditioning
Hzhertz
I/Oinput/output
ICinsulation contact
IECInternational Electrotechnical Commission
IFRindoor fan relay
in.inch
in.-lb.inch-pound
IPingress protection
IRinterrupting rating
K-ratingKelvin-rating
kcmilthousand circular mil
kgkilogram
kVkilovolt
kVAkilovolt-ampere
kWkilowatt
LEDlight-emitting diode
mmetre
m²square metre
mAmilliampere
MCCmotor control centre
minminute
mLmillilitre
mmmillimetre
mm²square millimetre
N•mnewton-metre
NACENational Association of Corrosion Engineers
NBCNational Building Code
NCnormally closed
NEMANational Electrical Manufacturers Association
NGRneutral grounding resistor
NMDnon-metallic dry
NMWnon-metallic wet
NMWUnon-metallic wet underground
NOnormally open
No.number
O.L.overload
PCBpolychlorinated biphenyl
PIRpassive infrared
PLCprogrammable logic controller
PPEpersonal protective equipment
PSpressure switch
PVCpolyvinyl chloride
rpmrotations per minute
RTRCreinforced thermosetting resin conduit
ssecond
SCRsilicon-controlled rectifier
SDSsafety data sheet
SQIMsquirrel-cage induction motor
SWDswitching duty
TCthermocouple
TRtimed relay
UPSuninterrupted power supply
Vvolt
VFDvariable frequency drive
Wwatt