Transformers, wye/delta and fault-current estimates
p/s: primary/secondary · N: turns · Z%: transformer nameplate percent impedance. Isc is a simplified terminal estimate with an infinite primary bus.
- Np/Ns = Vp/Vs = Is/Ip (ideal transformer)
- WyeVline = √3 × Vphase; Iline = Iphase
- DeltaIline = √3 × Iphase; Vline = Vphase
- Isc ≈ Irated / (Z% / 100)
- 1Keep primary and secondary ratios in the same orientation; current ratio is reversed.
- 2For a fault estimate convert percent impedance to a decimal.
A 480:120 V ideal transformer has a 4:1 ratio. A 40 A secondary load corresponds to 10 A primary current.
- Actual fault studies also require upstream and conductor impedance.
- Use the connection-specific line/phase relationship.
Pass Your Red Seal’s lessons and practice are independent study material. Source: OpenStax: transformers
Try one
An ideal transformer has 1000 primary and 250 secondary turns. If the primary is 480 V, what is the secondary voltage?