A steam-main drip leg collects condensate for a trap. A DP wet leg provides a reference head for level measurement; their purposes differ.

THE FORMULAS

  • Condensate formation rate ≈ heat loss rate / latent heat (consistent units)

HOW TO DO IT

  1. Identify low points, risers and equipment requiring drainage from the system layout.
  2. Check collector arrangement and trap differential pressure using the applicable steam-system guidance.
  3. Distinguish condensate-driven water hammer from thermal movement or control oscillation.

Worked example

With a stated 10 kW heat loss and 2000 kJ/kg latent heat, condensate forms at 10/2000=0.005 kg/s=18 kg/h. Trap selection must also allow for startup and operating conditions.

THE USUAL MISTAKES

  • Spacing and dimensions depend on the design and manufacturer; a rule of thumb is not a universal code requirement.
  • Water hammer can damage equipment; drainage is a system design concern.

SOURCES AND FURTHER READING

Pass Your Red Seal’s lessons and practice are independent study material. Manufacturer topics extend trade learning; they are not a claim about the content of an official exam.

TRY ONE · FREE

What is the primary purpose of installing drip legs at low points and at regular intervals along a steam distribution main?

Topic practice15 practice questions

Topic practice

15 practice questions
  • Choose a short set or the full topic
  • Review wrong answers and retry
  • Resume in this browser tab
Topic practice15 questions · 0 done